MPI-525 Multifunction Electrical Installation Meter WMGBMPI525

Description

Possible measurements

Short-circuit loop measurement:

  • impedance measurement with 23 A current (44 A phase-to-phase) – short-circuit resistor R=10,
  • measurement range: 95…440 V, frequency 45…65 Hz,

Short-circuit loop measurement with resolution 0,01, in distribution network without tiggering RCD (In30 mA):

  • automatic calculation of short-circuit, detection of phase voltage and phase-to-phase voltage,
  • additional UNI-Schuko plug for automatic measurement, AGT adapter for 3 phase network measurement.

Testing of general and selective RCD with the rated differential current of 10,30,100,300,500 and 1000 mA. (Type AC, A and B).

Measurement of insulation resistance:

  • with test voltage 250 V, 500 V, 1000 V, 2500 V,
  • measurement range up to 10G,
  • automatic discharging after measurement,
  • automatic measurement of all resistences in 3,4,5-wire cables using optional adapter AUTO-ISO,
  • acoustic signals in 5 sec intervals for insulation resistance characteristic,
  • elapsing T1, T2, T3 times (0…600 s) form measurement of absorption coefficients (DAR, PI or Ab1, Ab2)
  • safety measurement – protection against overvoltage.

Measurement of earthing resistance.

Bi-directional testing of PE wire continuity using 200 mA current.

  • Autocalibration of test leads.

Phase sequence testing.

Memory is divided into 10 memory banks each of them containing 99 memory cells.

Battery charge indicator.

AUTO-OFF function.

USB interface.

MPI-525 is equipment to perform complete test and verify on electrical installations according to the most common safety standards (IEC 61557, VDE 0100, BS7671).

Possible measurements

  • Short-circuit loop measurement:
    -impedance measurement with 23 A current (44 A phase-to-phase) – short-circuit resistor R=10 Ω,
    – measurement range: 95…440 V, frequency 45…65 Hz,
  • Short-circuit loop measurement with resolution 0,01 Ω, in distribution network without tiggering RCD (IΔn≥30 mA):
    – automatic calculation of short-circuit, detection of phase voltage and phase-to-phase voltage,
    – additional UNI-Schuko plug for automatic measurement, AGT adapter for 3 phase network measurement.
  • Testing of general and selective RCD with the rated differential current of 10,30,100,300,500 and 1000 mA. (Type AC, A and B).
  • Measurement of insulation resistance:
    – with test voltage 250 V, 500 V, 1000 V, 2500 V,
    – measurement range up to 10 GΩ,
    – automatic discharging after measurement,
    – automatic measurement of all resistences in 3,4,5-wire cables using optional adapter AUTO-ISO,
    – acoustic signals in 5 sec intervals for insulation resistance characteristic,
    – elapsing T1, T2, T3 times (0…600 s) form measurement of absorption coefficients (DAR, PI or Ab1, Ab2)
    – safety measurement – protection against overvoltage.
  • Measurement of earthing resistance.
  • Bi-directional testing of PE wire continuity using 200 mA current.
    – Autocalibration of test leads.
  • Phase sequence testing.
  • Memory is divided into 10 memory banks each of them containing 99 memory cells.
  • Battery charge indicator.
  • AUTO-OFF function.
  • USB interface.

Rated operational conditions:
– operation temperature 0…+50°C

Electric security:
– type of insulation: double, according to PN-EN 61010 – 1and IEC 61557, EMC
– measurement category: IV 300 V acc. to PN-EN 61010 – 1
– protection class acc. to PN-EN 60529: IP54

Short-circuit loop impedance measurement ZL-PE, ZL-N, ZL-L
Measurement using 23/40 A current measurement range in accordance with
IEC 61557: 0,13…1999,9 Ω
(for 1,2 m lead):

Range Resolution Accuracy
0,00…19,99 Ω 0,01 Ω ±(5% m.v + 3 dgt)
20,0…199,9 Ω 0,1 Ω
200…1999 Ω 1 Ω

rated voltage: 95…270 V (forZL-PE i ZL-N) and 95…440 V (for ZL-L)
frequency: 45…65 Hz

Short-circuit loop impedance measurement ZL-PE RCD
Measurement using 15 mA current measurement range in accordance with
IEC 61557: 0,50…1999,9 Ω

Range Resolution Accuracy
0,00…19,99 Ω 0,01 Ω ±(6% m.v. + 10 dgt)
20,0…199,9 Ω 0,1 Ω ±(6% m.v + 5 dgt)
200…1999 Ω 1 Ω

rated voltage: 95…270 V
frequency: 45…65 Hz

Measurement of earthing RE
Rated voltage in accordance with IEC 61557 – 5: 0,5…1999 Ω

Range Resolution Accuracy
0,00…9,99 Ω 0,01 Ω ±(2% m.v. + 4 dgt)
10,0…99,9 Ω 0,1 Ω ±(2% m.v. + 3 dgt)
100…999 Ω 1 Ω
1,00…1,99 kΩ 0,01 kΩ

 

Insulation resistance measurement
Measurement range in accordance with IEC 61557 – 2:
– for UN = 50 V: 50 kΩ…250 MΩ
– for UN = 100 V: 100 kΩ…500 MΩ
– for UN = 250 V: 250 kΩ…1 GΩ
– for UN = 500 V: 500 kΩ…2 GΩ
– for UN = 1000 V: 1 MΩ…3 GΩ
– for UN = 2500 V: 2,5 MΩ…9,99 GΩ

 

Range*) Resolution Accuracy
0…1999 kΩ 1 kΩ ±(3% m.v. + 8 dgt)
2,00…19,99 MΩ 0,01 MΩ
20,0…199,9 MΩ 0,1 MΩ
200…999 MΩ 1 MΩ
1,00…3,00 GΩ 0,01 GΩ ±(4% m.v. + 6 dgt)
1,00…9,99 GΩ 0,1 GΩ

 

 

*) limited to measurement range.
– with UNI-Schuko additional error ±2%.

Phase sequence
– phase sequence indicator: forward, reverse
– mains voltage range UL-L: 100…440 V (45…65 Hz) UL-L: 100…440 V (45…65 Hz)
– display of phase-to-phase voltages

Low voltage test of the circuit and insulation continuity
Test of PE wire continuity using a ±200 mA current

Range Resolution Accuracy
0,00…19,99 Ω 0,01 Ω ±(2% m.v. + 3 dgt)
20,0…199,9 Ω 0,1 Ω
200…400 Ω 1

– Voltage on open terminals: 4…9 V
– Test current at R<2 Ω: min. 200 mA at rated battery voltage
– Autocalibration of test leads
– Measurements for both polarizations of the current

RCD trigger and response time test tA (for tA mode)
Measurement ranges in accordance with IEC 61557: 0 ms … up to the upper bound of the displayed value

Breaker
Type
Test
Current
Multiplier
Measurement
Range
Resolution Accuracy
Standard 0,5*IΔn 0…300 ms 1 ms ± (2% m.v + 2 dgt)

 

1*IΔn
2*IΔn 0…150 ms
5*IΔn 0…40 ms
Selective 0,5*IΔn 0…500 ms
1*IΔn
2*IΔn 0…200 ms
5*IΔn 0…150 ms

Precision of the differential current: for 0,5*IΔn:-8…0% dla 1*IΔn, 2*IΔn, 5*IΔn: 0…8%

Measurement of the RCD triggering current (IA) for sine waveform testing current

Selected
Current
Range Resolution Test
Current
Accuracy
10 mA 3,3…10,0 mA 0,1 mA 0,3xIΔ..1,0xIΔ ± 5%IΔn
30 mA 9,0…30,0 mA
100 mA 33…100 mA 1 mA
300 mA 90…300 mA
500 mA 150…500 mA
1000 mA 330…1000 mA 1 mA

It is possible to start the measurement from the positive or negative half of the forced leaking current

Measurement of the RDC triggering current (IA ) for a unidirectional half period sine
waveform test current with a 6 mA direct current offset

Selected
Current
Range Resolution Test
Current
Accuracy
10 mA 4…20,0 mA 0,1 mA 0,4xIΔn..2,0xIΔn ±10%IΔn
30 mA 12,0…42,0 mA 0,4xIΔn..1,4xIΔn
100 mA 40,0…140 mA 1 mA
300 mA 120…420 mA
500 mA 200…700 mA

a measurement is possible for a positive or negative forced leakage current

Measurement of the RCD triggering current (IA ) for direct testing current

Selected
Current
Range Resolution Test
Current
Accuracy
10 mA 4,0…20,0 mA 0,1 mA 0,4xIΔn..2,0xIΔn ±10%IΔn
30 mA 12,0…60,0 mA 1 mA
100 mA 40…200 mA
300 mA 120…600 mA
500 mA 200…1000 mA

a measurement is possible for a positive or negative forced leakage current

„m.v.” measured value.

Reviews

There are no reviews yet.

Be the first to review “MPI-525 Multifunction Electrical Installation Meter WMGBMPI525”

Downloads

Data Sheet

User Manual

Declaration Of Conformity

More news coming soon

Courses Coming Up Soon

Like us on Facebook or subscribe to our Blog to stay up to date with upcoming training courses.